Specifications
Control Voltage: 24V (18-30 Vac) 50/60 Hz.
Current Draw: 0.2 A plus valve load @ 24Vac.
Trial for Ignition, Prepurge, Postpurge, Interpurge and ignition timings: Dependent on model ordered.
Ignition Sequence: Refer to the Normal Operating Sequence for Standard Models flowchart.
Flame Failure Response Time: 1 seconds maximum.
LED: The green status LED provides system status and error codes when in run mode, as well as when the system is attempting ignition.
Gas Control: Direct Ignition valves up to 2 A.
-
Minimum ambient temperature rating is -40°F (-40°C).
-
Maximum ambient rating is 175°F (79°C).
Relative humidity: 0% to 95% (non-condensing).
Approvals: UL 60730-1, UL 60730-2-5.