Operation


Normal Operation

The S8801 is powered by a 24 Vac transformer and is activated when the thermostat calls for heat. Operation is as follows (refer to the Normal Operating Sequence for Standard Models).

All models check for a false flame condition (short to ground) on a call for heat. Module will lock out for 1 hour if false flame condition is present. Reset could be manually done from the thermostat. If no false flame condition is present, operation continues.

Prepurge timing will begin on a call for heat, timing dependent on the model.

After the prepurge, power is supplied to a spark generator for spark ignition and the safety lockout timing begins. At the same time, the module opens the gas control's main valve which allows gas to flow to the main burner.

The igniter is on for approximately the first 80 percent of the ignition (or lockout timing) period. During the balance of the lockout timing period, the ignition is off and the flame sensor attempts to prove the flame. The flame is considered proved when current from the flame sensor through the burner flame to ground reaches 1.5 μA dc.

If flame is proved, the gas control remains open and the burner stays on until the call for heat ends.

If flame is not proved, or if current flow is interrupted, i.e., flame-out condition, the trial for ignition begins again.

The S8801 will keep the gas control main valve open as long as there is a call for heat and there is enough flame current sensed. If, however, the safety lockout timing period ends before the main burner lights or the flame sensor establishes enough current, the system will go into safety lockout for 1 hour (if exceeded number of trials).

When the system goes into safety lockout, power to the spark generator is interrupted, the gas control circuit is interrupted, and the alarm circuit is completed and LED will flash 2 times. The system will stay locked out for one hour or until it is reset by moving the thermostat set point below room temperature so there is no call for heat for at least 1 minute.

For a summary of the normal operating sequences across all standard models, refer to the Normal Operating Sequence for Standard Models.


Failed trial for ignition

If the main burner flame is not lit and sensed before the end of the ignition trial time, the control shuts off the gas valve (100% shutoff) and either retries or locks out for 1 hour before trying again (model dependent). If it goes into lockout, the control will remain in lockout for 1 hour or until power to the control is cycled by the system thermostat or by removing and restoring system power.

 

Normal Operating Sequence for Standard Models