Specifications
Control Voltage: 24V (18-30 Vac) 50/60 Hz.
Current Draw: 0.2 A plus valve load @ 24Vac.
Trial for Ignition, Prepurge, Postpurge, Interpurge and ignition timings: Dependent on model ordered.
Ignition Sequence: Refer to the Normal Operating Sequence for Standard Models flowchart.
Flame Failure Response Time: 1 seconds maximum.
LED: The green status LED provides system status and error codes when in run mode, as well as when the system is attempting ignition.
Gas Control: Direct Ignition valves up to 2 A.
-
Minimum ambient temperature rating is -40°F (-40°C).
-
Maximum ambient rating is 175°F (79°C).
Relative humidity: 0% to 95% (non-condensing).
Approvals: UL 60730-1, UL 60730-2-5.
Hot Surface Igniter or Igniter-sensor: Norton Model 201 or 271, or equivalent.
NOTE: If an igniter other than Norton Model 201 or 271 is used, the igniter must meet the following minimum specifications, required over the life of the igniter:
-
Igniter must reach 1832 °F (1000 °C) within 34 seconds with 102 Vac applied.
-
Igniter must maintain at least 500M ohms insulation resistance between the igniter lead wires and the igniter mounting bracket.
-
Igniter must not develop an insulating layer on its surface (over time) which would prevent flame sensing.
-
Igniter surface area immersed in flame must not exceed 1/4 of the grounded area immersed in flame. This would prevent flame sensing.
-
Igniter current draw at 132 Vac must not exceed 5 A.